500-Ton Air Cooled Chiller

The air-cooled chiller cooling process is broken down into two parts which are the absorption of heat from processed water and subsequent transfer of heat into the atmosphere. These chillers are typically used when there is a lack of space for the unit(s) where the magnitude of discharged heat load is irrelevant.

Description

The air-cooled chiller cooling process is broken down into two parts which are the absorption of heat from processed water and subsequent transfer of heat into the atmosphere. These chillers are typically used when there is a lack of space for the unit(s) where the magnitude of discharged heat load is irrelevant.

Model #30XAA5006J-02N13

Our air-cooled chillers are available in capacities ranging from 10 to 500 tonnes (applications down to 1 tonne available).

Features

  • Ready for outdoor operation with minimal setup
  • Complete microprocessor control center
  • Trailer-mounted
  • Dual point power connection
  • Pre-wired pump, 1200 gpm @ 100 ft-head
  • Low ambient temperature operation to 0°F
  • Brine mode to 25°F
  • 300 psig water pressure option available

Additional information

Water Connections

6" 150 lb RF flange in/out

Water Volume

93 gallons

Water Max. Pressure

150 psig

Minimum Load

42 tons

Min / Max Water Flow

800 / 2004 gpm

Circuits/Compressors

2 / 3

Refrigerant/Charge

R134a / 205 / 415 / 415 lb

Oil/Charge

POE / 7.5 / 6.3 / 7.5 gal.

Shipping Weight

38,000 lbs (chiller)

Dimensions

48’ L x 8’ W x 8 ½‘ H

Leveling Required

Within 1” per 8'

Installed Clearances

10’ (sides), 4’ (electrical)

Voltage

460V / 3 phase / 60 hertz

Disconnect Size

1000 amps / 1000 amps

Connections

Leviton Series 16 Cam

Cables Circuit 1

4/0 – (2) Per Ph, (1) Gnd

Cables Circuit 2

4/0 – (3) Per Ph, (1) Gnd

FLA/MCA Circuit 1

377 / 447 amps (w/pump)

FLA/MCA Circuit 2

528 / 604 amps

Rec. Service

600 / 800 amps